VS High-Precision Voltage Transducer

The VS series voltage transducer is a wide-range sensor covering up to 35 kV DC, AC, periodic pulses, and arbitrary waveforms. Delivering accuracy to 0.05 % FS and bandwidth up to 100 kHz, it meets the demands of broadband, high-precision voltage measurement.
VS High-Precision Voltage Transducer (1)

Wide-bandwidth measurement range

The VS high-precision voltage transducer offers an input test bandwidth of up to 100 kHz [1], making it ideal for wide-band PWM waveforms, complex voltage waveform sampling, and harmonic analysis.
VS High-Precision Voltage Transducer (2)

Clearly defined phase-angle error specification

Conventional voltage transducers only specify ratio error and provide no phase-angle rating; they are thus suitable only for stand-alone voltage measurement. When the transducer is used for power measurement, however, the phase-angle error becomes a critical factor affecting accuracy. The VS series voltage transducers feature a clearly defined phase-angle specification, with a typical phase displacement as low as 1 arc-minute, making them the preferred choice for power-measurement applications.

The table below lists the power-measurement error caused by a 10′ phase-angle error (≈0.0029 rad, equivalent to the error limit of a class 0.2 electromagnetic transformer) as the phase angle varies from 0° to 90°:

Serial Number

Phase angle(°)

cos Φ

tan Φ

Power error caused by phase-angle deviation (%)

1

30

0.866

0.5774

0.17

2

60

0.5

1.7321

0.5

3

78.5

0.1994

4.9152

1.4

4

87.1

0.0506

19.74

5.7

5

88.9

0.0192

52.081

15

As shown in the table, phase-angle error has a significant impact on power measurements, becoming especially pronounced under low power-factor conditions. The VS high-precision voltage transducer delivers a typical phase displacement of only 2 arc-minutes, an outstanding specification that effectively safeguards power-measurement accuracy.